Figure 4-31 Basic Param.
Item
Number of
iBOXs
Start address
for iBOX-NMS
communicati
on
iBAT number
of iBOX
Figure 4-32 Advanced Param.
Item
Current
source
Batt.
abnormal
BCB trip
Issue 05 (2024-01-30)
Description
Specifies the number of
iBOXs connected to the UPS.
Specifies the communication
address when the
northbound device queries
iBOX data.
Specifies the number of
N
iBATs managed by the iBOX.
Description
Specifies the specifications of
the Hall effect sensor used to
detect iBOX current.
Specifies whether BCB trips
when batteries are abnormal.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
0
0–6
0
0–124
0
0–300
Default Value
Value Range
200 A
Hall sensor
200A, Hall
sensor 600A
Disable
Disable,
Enable
128