Huawei UPS5000-E-60K-F60 User Manual page 138

Hide thumbs Also See for UPS5000-E-60K-F60:
Table of Contents

Advertisement

UPS5000-E-(60 kVA-160 kVA)
User Manual (Low Voltage)
Item
MUE05A connection
Batter ground fault [BTG]
D.G. connection [GEN]
BCB connection [OL]
Battery breaker [STA]
PDC output breaker [OUT]
PDC maintenance breaker
[MT]
BP/SYSMT Switch
BP/SYSMT switch function
SPD/SYSOUT Switch
SPD/SYSOUT switch function
Issue 05 (2024-01-30)
Monitoring interface card (MUS05A): provides four routes of configurable
output dry contact signals.
Dry contact extended card (MUE07A): currently provides five input and five
output signals.
Copyright © Huawei Digital Power Technologies Co., Ltd.
Description
Specifies the MUE05A connection status.
Independent input signals can be enabled only
when this parameter is set to Enable.
Specifies whether to enable or disable battery
grounding fault detection.
Specifies whether to enable or disable DG
connection status detection.
Specifies whether to enable or disable BCB
connection status detection.
Specifies whether to enable or disable battery
circuit breaker status detection.
Specifies whether to enable or disable PDC
output circuit breaker status detection.
Specifies whether to enable or disable PDC
maintenance circuit breaker status detection.
BP/SYSMT switch: bypass input/system
maintenance switch.
If the BP/SYSMT switch is set to Enable, the
port has dry contact signal access. How to use
the port depends on the status of the BP/SYSMT
switch.
If the BP/SYSMT switch is set to Enable, this
parameter is displayed on the screen. Set this
parameter to determine whether the port is
used to detect the status of the PDC bypass
input circuit breaker or system maintenance
circuit breaker.
SPD/SYSOUT switch: SPD/system output switch.
If the SPD/SYSOUT switch is set to Enable, the
port has dry contact signal access. How to use
the port depends on the status of the SPD/
SYSOUT switch.
If the SPD/SYSOUT switch is set to Enable, this
parameter is displayed on the screen. Set this
parameter to determine whether the port is
used to detect the status of the PDC input SPD
or system output circuit breaker.
4 User Interface
130