User Manual (Low Voltage)
Item
RAM verification
Collect real-time
site waveform
Fan life
Pre-warn. time for
fan life (mon)
Key update interval
(d)
BCB trips in case of
EOD
Table 4-13 Input Settings
Item
Input adaptability
Table 4-14 Output Settings
Item
Zero display with no
load output
Issue 05 (2024-01-30)
Description
Specifies whether to enable the memory
check function. If this parameter is set to
Enable, the control chip RAM working
status is checked regularly. If this
parameter is set to Disable, regular check
is disabled.
If this parameter is set to Enable, one
waveform can be stored manually.
Specifies whether to enable the life
detection for fans in the power modules
and bypass modules.
When the Fan lifespan left is less than the
setting, an alarm is generated.
-
If this parameter is set to Enable, the BCB
trips in case of EOD.
Description
Input adaptability mode 1: It is applicable to
normal power grids, normal DGs, and DGs
that are sensitive to the output reactive
component. Input adaptability mode 2: It is
applicable to normal power grids, normal
DGs, and input power sources with high
internal resistance.
Description
If this parameter is set to Enable, the
output current is displayed as 0 with no
load output, and the output load rate is
displayed as 3%. When this parameter
is set to Disable, the output current and
output load rate are not 0.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 User Interface
Default
Value Range
Value
Disable
Disable, Enable
Disable
Disable, Enable
Enable
Disable, Enable
12
1–24
180
30–1095
Enable
Disable, Enable
Default
Value Range
Value
Mode 2
Mode 1, Mode 2
Default
Value Range
Value
Enable
Disable, Enable
142