UPS5000-E-(60 kVA-160 kVA) User Manual (Low Voltage) Issue Date 2024-01-30 HUAWEI DIGITAL POWER TECHNOLOGIES CO., LTD.
Page 2
Notice The purchased products, services and features are stipulated by the contract made between Huawei Digital Power Technologies Co., Ltd. and the customer. All or part of the products, services and features described in this document may not be within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements, information, and recommendations in this document are provided "AS IS"...
100 kVA, 120 kVA, 140 kVA, and 160 kVA. NO TE ● The UPS5000-E-60K-F60 with a capacity of 20 kVA, 40 kVA, or 60 kVA has the same specifications as the UPS5000-E-100K-F100 with a capacity of 20 kVA, 40 kVA, or 60 kVA respectively.
The UPS5000-E provides a variety of optional components to address various customer requirements. Ease of Use ● The UPS5000-E is maintained from the front. UPS5000-E-60K-F60 and UPS5000-E-100K-F100 can be installed back to back or in a row against the wall to save space. ●...
User Manual (Low Voltage) 3 Installation 3.2 Installing a Single UPS NO TICE ● The top outlet kit apply only to the UPS5000-E-60K-F60 and UPS5000-E-100K- F100. ● The other components are optional for the three models of UPS5000-Es. 3.2.1 Installing the UPS Cabinet Secured Installation Step 1 Determine the cabinet installation position.
3.2.5.1 Top Cable Routing Context NO TICE ● The cable connection procedures for the UPS5000-E-60K-F60 and UPS5000- E-100K-F100 are the same. The following describes how to connect cables for the UPS5000-E-100K-F100. ● Route cables for the UPS from inside out.
3.2.7 Connecting a Remote EPO Switch NO TICE ● Huawei does not provide the EPO switch or cable. Prepare them by yourself. The recommended cable is 22 AWG. ● Equip the EPO switch with a protective cover to prevent misoperations, and protect the cable with a protective tube.
User Manual (Low Voltage) 3 Installation 3.3.3 Connecting Signal Cables Context A maximum of two UPS5000-E-60K-F60, UPS5000-E-100K-F100, or UPS5000- E-160K-F160 products can be connected in parallel. Procedure Step 1 Connect the parallel ports on the UPSs using parallel cables. ●...
Page 144
Bus Capa. Life If the service life of a capacitor is about to end, that is, Module X bus capacitor life (y) is less than 1.0, contact Huawei technical support to replace the power module. Fan Lifespan Estimate ●...
Before powering on the UPS, ensure that all the UPS switches and upstream switch are OFF. Procedure Step 1 Close the upstream bypass and mains input switches. After the UPS is powered on, initialization begins. The MDU displays the Huawei logo and an initialization progress bar. ----End Issue 05 (2024-01-30)
Step 4 Press and hold down the BATT START button on the bypass module for at least 2 seconds. The system automatically enters the battery cold start state. The MDU displays the Huawei logo and an initialization progress bar. Step 5 After initialization, start the inverter on the LCD.
BATT START button on the UPS bypass module for more than 2 seconds. The system automatically enters the battery cold start state. The MDU displays the Huawei logo and an initialization progress bar. Step 6 After initialization, start the inverter on the LCD.
Customers are not allowed to maintain components behind protective covers that can be removed only using tools. If the components are to be maintained, contact Huawei technical support. ● Only maintenance engineers can maintain power modules and bypass modules.
Communicatio Dry contacts, RS485, and SNMP Weight ● UPS5000-E-60K-F60: 291 kg. Each power module is 32 kg. A maximum of three power modules are supported. ● UPS5000-E-100K-F100: 355 kg. Each power module is 32 kg. A maximum of five power modules are supported.