Clearances; Tools - Huawei UPS5000-E-60K-F60 User Manual

Hide thumbs Also See for UPS5000-E-60K-F60:
Table of Contents

Advertisement

UPS5000-E-(60 kVA-160 kVA)
User Manual (Low Voltage)

3.1.1.3 Clearances

Reserve the following clearances around the cabinet to facilitate operations and
ventilation:
Figure 3-2 Reserved clearances (unit: mm)

3.1.2 Tools

The onsite operation personnel can select tools based on the site requirements.
Issue 05 (2024-01-30)
Do not install the UPS in environments with conductive metal scraps in the
air.
The optimal operating temperatures for valve-regulated lead-acid (VRLA)
batteries are 20–30°C. Operating temperatures higher than 30°C shorten the
battery lifespan, and operating temperatures lower than 20°C reduce the
battery backup time.
Reserve a clearance of at least 800 mm from the front of the cabinet.
Reserve a clearance of at least 500 mm from the top of the cabinet.
If there is a top outlet kit (without antiseismic kits), the cabinet can be
installed against the wall and no space needs to be reserved at the rear. If
there is no top outlet kit, reserve a clearance of at least 500 mm at the rear
for ventilation. If operations need to be performed at the rear, reserve a
clearance of at least 800 mm for operations.
Copyright © Huawei Digital Power Technologies Co., Ltd.
3 Installation
48

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ups5000-e-100k-f100Ups5000-e-160k-f160

Table of Contents