UPS5000-E-(60 kVA-160 kVA)
User Manual (Low Voltage)
● Ensure that the load power is stable. If the system load power fluctuation is
● Check whether the number of UPS redundant modules and the number of
WebUI
1.
2.
Old WebUI
1.
2.
Issue 05 (2024-01-30)
NO TICE
greater than the rated capacity of half a module (for example, the single-phase
load power fluctuation is greater than 8.33 kVA for a 50 kVA module), the UPS
may enter and exit hibernation mode repeatedly.
racks are appropriate. If the number is insufficient, the UPS may not enter
hibernation mode.
On the WebUI, choose Monitoring > UPS System > Running Parameter >
System Settings, and set Paral sys hibernate to Enable.
Set Module cycle hiber. period (d) to an integer ranging from 1 to 100. The
default value is 30.
Figure 5-24 Hibernation parameters
NO TE
Click Submit after setting parameters on the WebUI.
On the WebUI, choose Monitoring > Parameter Settings > System Settings,
and set Paral. sys. hibernate to Enable.
Set Module cycle hiber. period (d) to an integer ranging from 1 to 100. The
default value is 30.
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Operations
203