UPS5000-E-(60 kVA-160 kVA)
User Manual (Low Voltage)
Item
EOD restart
EOD restart
delay (min)
Bypass Settings
Figure 4-27 Bypass Settings
Issue 05 (2024-01-30)
Description
The UPS transfers to battery
mode when the mains is
abnormal. When batteries
reach the end of discharge
(EOD) threshold and the
bypass is unavailable, the
UPS powers off. After the
mains recovers, the UPS will
automatically restart if EOD
restart is set to Enable.
If EOD restart is set to
Disable, manually rectify the
fault and restart the UPS or
enable the EOD restart
function.
If EOD restart is set to
Enable, the UPS starts
working after the time set for
EOD restart delay when the
input recovers from a power
failure upon battery EOD.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
Enable
Disable,
Enable
10
1–1440
123