UPS5000-E-(60 kVA-160 kVA)
User Manual (Low Voltage)
Item
Bus overvolt.
recovery time
Capacitor
failure
detection
Bypass Settings
Item
BPM mode
upon BPM
overtemp.
Issue 05 (2024-01-30)
Description
If Bus overvoltage recovery
is set to Enable, the bus
overvoltage alarm is
automatically cleared, and
the rectifier and inverter
automatically start when the
bus voltage recovers (less
than 420 V) within Bus
overvolt. recovery time.
If this parameter is set to
Enable, the inverter
capacitor fault detection is
performed based on the
settings of Capacitor failure
detection upper limit and
Capacitor failure detection
lower limit. If the inverter
capacitor is faulty, the power
module shuts down the
inverter to prevent the fault
from escalating.
Description
Specifies whether to start
bypass mode when
overtemperature occurs.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
5s
5s, 1 min, 5
min, 10 min
Disable
Disable,
Enable
Default Value
Value Range
Enable
Disable,
Enable
159