Optional) Setting Parameters For The Bcb Box; Shutting Down And Powering Off The Ups - Huawei UPS5000-E-60K-F60 User Manual

Hide thumbs Also See for UPS5000-E-60K-F60:
Table of Contents

Advertisement

UPS5000-E-(60 kVA-160 kVA)
User Manual (Low Voltage)
Procedure
Step 1 After confirming that the battery strings are properly connected, close the battery
string input circuit breaker. If there are multiple battery strings, close the circuit
breaker for each battery string and then the general circuit breaker between
battery strings and the UPS. The No battery alarm disappears from the MDU.
Step 2 Close the UPS downstream output switch to supply power to the loads.
----End

5.1.5 (Optional) Setting Parameters for the BCB Box

Prerequisites
A BCB box is installed.
Procedure
Step 1 On the System Info > Settings > Dry Contact Set screen, set MUE05A
connection to Enable, and set BCB connection [OL] and Battery breaker [STA]
to Enable.
Figure 5-4 BCB connection setting
----End

5.2 Shutting Down and Powering Off the UPS

Context
After the inverter is shut down, if the bypass is normal, the UPS transfers to
bypass mode; if the bypass is not normal, the UPS supplies no power. Before
shutting down the UPS, ensure that all loads have been shut down.
Issue 05 (2024-01-30)
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Operations
186

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ups5000-e-100k-f100Ups5000-e-160k-f160

Table of Contents