Huawei UPS5000-E-60K-F60 User Manual page 144

Hide thumbs Also See for UPS5000-E-60K-F60:
Table of Contents

Advertisement

UPS5000-E-(60 kVA-160 kVA)
User Manual (Low Voltage)
Before performing Wizard Startup, ensure that:
● The system is a single UPS system.
● No minor or critical alarm is generated.
● The UPS works in normal mode with a load rate fluctuation less than 10%.
● The UPS does not generate any battery overtemperature, overvoltage, or
● The mains, batteries, charger, and discharger are normal. No overload alarm is
● The SOC is greater than 30%.
Figure 4-41 Wizard Startup
On the System Info > Settings > Dry Contact Set screen, set MUE05A connection to Enable,
and set BCB connection [OL] to Enable. Wizard Startup can be used to test the battery switch
tripping function.
Bus Capa. Life
If the service life of a capacitor is about to end, that is, Module X bus capacitor
life (y) is less than 1.0, contact Huawei technical support to replace the power
module.
Fan Lifespan Estimate
Issue 05 (2024-01-30)
NO TICE
overcurrent alarm. No generator is connected to the UPS.
generated.
NO TE
If the service life of a fan is about to end, that is, Module X fan life (y) is less
than Pre-warn. time for fan life(mon), contact Huawei technical support to
replace the power module.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 User Interface
136

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ups5000-e-100k-f100Ups5000-e-160k-f160

Table of Contents