Huawei UPS5000-E-60K-F60 User Manual page 191

Hide thumbs Also See for UPS5000-E-60K-F60:
Table of Contents

Advertisement

UPS5000-E-(60 kVA-160 kVA)
User Manual (Low Voltage)
Figure 5-1 Settings wizard
Step 4 After you set parameters on the Settings Wizard screen, the system displays the
Bypass mode and No battery alarms, which do not need to be handled. Other
alarms need to be handled.
Step 5 If the system has connected to the remote EPO switch, you need to choose
Monitoring > UPS System > Running Parameter > System Settings on the
WebUI and set EPO detection to Enable.
Issue 05 (2024-01-30)
NO TE
● Set the time and date correctly. Incorrect time and date will lead to false fault analysis
during maintenance or repair, affecting the normal operation.
● After network parameters are set, connect the UPS to the network, ensuring that
maintenance personnel can manage or control the UPS remotely. If remote
management is not needed, retain the default network parameter settings.
NO TE
● After you set parameters on the Settings Wizard screen, choose System Info > Settings
> System Settings. Check that Requisite modules and Redundant modules match the
actual values.
● If dry contact signals are connected to the system, choose System Info > Settings > Dry
Contact Settings. Check that the connected dry contacts have been enabled and that
the disconnected dry contacts have been disabled.
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Operations
183