2-Axis Fixed-Feed Control (Interpolation) - Mitsubishi Electric MELSEC-QD75MH1 User Manual

Positioning module
Table of Contents

Advertisement

9 MAJOR POSITIONING CONTROL

9.2.7 2-axis fixed-feed control (interpolation)

In "2-axis fixed-feed control" ("
used to carry out fixed-feed control in a linear path while carrying out interpolation for
the axis directions set in each axis.
In fixed-feed control, any remainder of the movement amount designated in the
positioning data is rounded down if less than that required for control accuracy to
output the same amount of pulses. (The remainder of the movement amount with an
accuracy below the control accuracy does not affect the regular controls.)
(Refer to Section 9.1.6 "Interpolation control" for details on interpolation control.)
Operation chart
In incremental system 2-axis fixed-feed control, the addresses (
feed value) of the current stop position (start addresses) of both axes are set to
"0". Linear interpolation positioning is then carried out from that position to a
position at the end of the movement amount set in "
address/movement amount". The movement direction is determined by the sign of
the movement amount.
Y axis
" Md. 20 Current feed value" of each axis
is set to "0" at the positioning start
Designated movement
amount
Restrictions
(1) An axis error "Continuous path control not possible (error code: 516)" will
occur and the operation cannot start if "continuous path control" is set in
Da.1
"
Operation pattern". ("Continuous path control" cannot be set in fixed-
feed control.)
(2) "Fixed-feed" cannot be set in "
when "continuous path control" has been set in "
the immediately prior positioning data. (For example, if the operation pattern of
positioning data No. 1 is "continuous path control", fixed-feed control cannot
be set in positioning data No. 2.) An axis error "Continuous path control not
possible (error code: 516)" will occur and the machine will carry out a
deceleration stop if this type of setting is carried out.
Da.2
Control system" = fixed-feed 2), two motors are
(0,0)
(0,0)
Designated movement
amount
Da.2
Control system" in the positioning data
9 - 46
MELSEC-Q
Md.20
Current
Da.6
Positioning
(0,0)
Da.1
Operation pattern" of
X axis

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec-q seriesMelsec-qd75mh2Melsec-qd75mh4

Table of Contents