4 INSTALLATION, WIRING AND MAINTENANCE OF THE PRODUCT
20cm(7.88inch)
to 30cm(11.82inch)
(5) To make this product conform to the EMC directive and low voltage
instruction, be sure to used of a AD75CK type cable clamp (manufactured
by Mitsubishi Electric) for grounding connected to the control box and the
shielded cable.
Inside control box
AD75CK
[How to ground shielded cable using AD75CK]
Shielded cable
Shield
Using the AD75CK, you can tie four cables of about 7mm outside diameter together for
grounding.
Ground terminal installation screw (M4 8 screw)
Installation screw to control box (M4 screw)