Window Size; Teach 12 Ma (5 V) - Banner LTF Series Instruction Manual

Time of flight laser distance sensor
Hide thumbs Also See for LTF Series:
Table of Contents

Advertisement

3.5.2.1. Window Size

The A_OUT > TchMid > WndSize option sets the window size that the Midpoint TEACH uses to set the 4 mA (0 V) and 20 mA (10 V) setpoints.
The taught surface must be inside the defined sensing range, and at least one setpoint (with offset applied, if any) must be located within the
sensing range.
The Analog Output window size is a different setting than the Discrete Output window size when defined using the push buttons.
Parameters
Window Size Minimum
Window Size Maximum
Range
Default Window Size
Navigate: MENU > A_OUT > TchMid > WndSize
Remote Input: Available
1)
Access the Window Size mode.
Method
Push Button
Navigate: MENU > A_OUT > TchMid > WndSize
a. Double-pulse the remote input to enter setup mode.
Remote Input
b. Three-pulse the remote input to enter window size
mode.
2)
Set the window size.
Method
a. Use the Up and Down buttons to set the desired window size—the value changes in
increments of 2.
Push Button
b. Press Enter to save the new value.
Pulse the remote input 1 to 6 times to select the desired window size.
1 pulse: 10 mm
Remote Input
2 pulses: 20 mm
(Sets A_OUT and
3 pulses: 100 mm
D_OUT window
4 pulses: 500 mm
Size)
5 pulses: 2000 mm
6 pulses: 11950 mm for the LTF12; 23950 mm for the LTF24

3.5.2.2. TEACH 12 mA (5 V)

The Tch12mA (Tch5V) option sets the midpoint that determines the actual measurement window.
Navigate: MENU > A_OUT > TchMid > Tch12mA (Tch5V)
Remote Input: Available
Button Instructions
1)
Present the target.
Present the target.
2)
Access the TEACH 12 mA (5 V) mode and TEACH the sensor.
LTF12
10 mm
11950 mm
50 mm to 12000 mm
2000 mm
Action
Action
Action
© Banner Engineering Corp. www.bannerengineering.com
10 mm
23950 mm
50 mm to 24000 mm
2000 mm
"WndSize" and the current window size value
display.
T
T
a. "REMOTE SETUP" displays.
T
b. "WndSize" and the current window size
T
T
T
value display.
T
T
a. "WndSize" and the new value
display.
b. The new value flashes and the sensor
returns to "TchMid WndSize".
The new value flashes and the sensor
returns to Run mode.
The target's analog output measurement and distance
measurement values display.
S
P
ENSOR
ROGRAMMING
LTF24
Result
Result
Result
12

Advertisement

Table of Contents