Actuator Operation From Remote - AUMA PROFOX PF-Q80 Operation Instructions Manual

Part-turn actuators
Hide thumbs Also See for PROFOX PF-Q80:
Table of Contents

Advertisement

Password A specific password is assigned to each user level and allows different actions. The

8.2.3 Actuator operation from Remote

CAUTION
AUMA Assistant App
M
AUMA CDT
M
6 different users/user levels are available. User level (1), (2), (3), ... is indicated in the
top display row.
Figure 32: User level display (example user level 4)
password must comprise 6 characters.
Table 20: User level and password
User levels and authorisations
User (user level)
Observer (1)
Operator (2)
Maintenance (3)
Specialist (4)
Service (5)
AUMA (6)
Unauthorised access is made easier due to insecure password! Therefore, we re-
commend changing the password during initial commissioning.
Risk of immediate actuator operation when connecting to mains!
Risk of personal injuries or damage to the valve.
à Check operation signals and operation behaviour prior to switching on the mains
voltage.
à Ensure that the tripping conditions for the failure behaviour are not fulfilled when
switching on.
à Ensure that the tripping conditions for the EMERGENCY behaviour are not fulfilled
when switching on.
Operation mode REMOTE setting
Operation mode REMOTE is the preliminary condition for actuator control via digital
inputs, analogue inputs or via fieldbus.
The operation mode can be activated via AUMA Assistant App or AUMA CDT soft-
ware:
[DIS_53] Configuration
 [DIS_2919] Operation mode
  [PRM_5535] Selector
Or directly via the Remote operation menu in [DIS_2250] Operation function.
Default setting: Operation mode = REMOTE
[DIS_53] Configuration
 [DIS_2919] Operation mode
  [PRM_5535] Selector
Or directly via the tool bar in the "Device" tab in [PRM_5535] Selector or Remote con-
trol.
Authorisation/password
Verify settings
No password required
Change configuration parameters (low level)
Factory password: 000000
Reserved for future use
Change configuration parameters (high level)
e.g. type of seating, assignment of output contacts
Factory password: 000000
Service staff
Modify configuration parameter (scope of service)
AUMA administrator
Operation