PowerCube 1000 (STC, Saudi Arabia, ICC800-A1-C2,
ESC800-A1)
Installation Guide
Item
Alarm
indicator
Fault
indicator
Technical Specifications
Table 3-27 M48500N1 technical specifications
Item
Input voltage range
Issue 02 (2021-09-28)
Color
Status
Yellow
Steady on
Off
Blinking
slowly (0.5
Hz)
Red
Off
Steady on
Specifications
40–60 V DC
Copyright © Huawei Technologies Co., Ltd.
Description
● An ambient overtemperature alarm is
generated.
● Overtemperature protection is
triggered.
● Undertemperature protection is
triggered.
● The 12 V DC, 24 V DC, or 24 V AC
output is turned off.
● The power module is hibernating. (In
this mode, only the protection indicator
is on and no alarm is reported.)
● A DC input overvoltage or
undervoltage alarm is generated.
● The 12 V DC, 24 V DC, or 24 V AC
output experiences overcurrent, short
circuit, or over power.
The power module is normal.
The power module fails to communicate.
The power module is normal.
● Internal communication fails.
● The fan is faulty.
● The power module shuts down due to
output overvoltage.
● The power module shuts down due to
internal overtemperature.
● No output or emergency shutdown due
to internal causes.
● A 12 V DC, 24 V DC, or 24 V AC output
undervoltage alarm is generated.
● The switch on the panel of the module
is OFF.