PowerCube 1000 (STC, Saudi Arabia, ICC800-A1-C2,
ESC800-A1)
Installation Guide
Item
Operating
temperature
Transportation
temperature
Storage temperature
Operating humidity
Altitude
Noise level
IP rating and
operating
environment
Other requirements
Issue 02 (2021-09-28)
Specifications
0°C to +45°C (with solar radiation)
–40°C to +70°C
–40°C to +70°C
5%–95% RH (non-condensing)
0–4000 m. When the altitude ranges from 2000 m to
4000 m, the operating temperature decreases by 1°C for
each additional 200 m.
GR487, acoustic pressure level ≤ 65 dBA at 1.5 m
(ambient temperature 45°C)
IP55, Class C environments
● There should be no conductive dust, corrosive gas, or
explosion hazard.
● Dust, corrosive substances, pests, molds, and other
indicators should be controlled in accordance with
Class 4.1 requirements in ETSI EN 300 019-1-4
(V2.2.1).