Setting The Branch User And Load Type; Setting Customized Load Disconnection Parameters - Huawei PowerCube 1000 Installation Manual

Table of Contents

Advertisement

PowerCube 1000 (STC, Saudi Arabia, ICC800-A1-C2,
ESC800-A1)
Installation Guide
Table 12-5 Setting basic branch parameters on the LCD
Main Menu
Second
-Level
Menu
Parameters
Digital
Settings
Power

12.2.4.3 Setting the Branch User and Load Type

If branch usage is set to BLVD Load or Customized Load, you can set the user
and load type.
Table 12-6 Setting basic branch parameters on the LCD
Main
Second-Level
Menu
Menu
Parameters
Digital Power
Settings

12.2.4.4 Setting Customized Load Disconnection Parameters

Context
Issue 02 (2021-09-28)
Third-Level
Fourth-Level
Menu
Menu
DC Output
Load Branch
Distribut.
n
General
Power
Distribution
Branch n
Battery
Power
Distribution
Branch n
Third-Level
Menu
DC Output
Distribut.
Voltage mode: When an AC power failure occurs, you can perform
disconnection management based on the battery discharge voltage.
Consumption mode: When an AC power failure occurs, disconnection
management is performed based on the backup power configured for the
load branch.
Capacity mode: When an AC power failure occurs, you can perform
disconnection management based on the battery discharge capacity.
Copyright © Huawei Technologies Co., Ltd.
Fifth-Level
Menu
Customized
Breaker
Capacity
Customized
Breaker
Capacity
Customized
Breaker
Capacity
Fourth-Level
Fifth-Level
Menu
Menu
Load Branch
User
12 Power-on and Commissioning
Default
Value Range
Value
Rated
3 A to rated
Circuit
capacity of the
Breaker
circuit breaker
Capacity
NOTE
● Set the circuit
Rated
breaker
Circuit
capacity based
Breaker
on the actual
Capacity
load current.
● The capacity of
Rated
the circuit
Circuit
breaker cannot
Breaker
exceed the
through-
Capacity
current
capacity of the
cable and the
rated capacity
of the circuit
breaker.
Default
Value
Value
Range
None
User 1 to
user 10,
None
125