PowerCube 1000 (STC, Saudi Arabia, ICC800-A1-C2,
ESC800-A1)
Installation Guide
Table 3-6 Intelligent circuit breaker (iCBD)
Circuit Breaker Slot No.
The number indicated by the arrow is the slot
number of the circuit breaker. On the LUI,
WebUI, or NMS, the circuit breaker slot number
corresponds to the branch number, such as
branch 17 and branch 19 in the preceding
figure.

3.7 DC Output Box

Figure 3-15 DC output box panel (ICC800-A1-C2)
(1) DC output circuit breakers
Table 3-7 PDU specifications
Item
DC power distribution
Installation mode
Issue 02 (2021-09-28)
NO TE
The intelligent circuit breaker is powered by the UIM. If the UIM is faulty or removed, the
intelligent circuit breaker cannot be switched on or off over remote management or local
LUI. In this case, you can only operate the circuit breaker handle to switch on or off the
intelligent circuit breaker.
Copyright © Huawei Technologies Co., Ltd.
Feature
The intelligent circuit breaker integrates the
power-off and measurement functions.
(2) RTN+ terminal
DC output box
DC output: 2 x 32 A/1P, 2 x 16 A/1P and 2 x 6
A/1P circuit breakers
Installed on the cabinet side panel.