12.2.11 Setting Multiplexed Dry Contact Ports Type
Context
ALMn/DINn on the silk screen of the UIM indicates that they are multiplexed
ports. By default, they are ALM output ports. You can set the multiplexed port to a
DIN input dry contact or an ALM output dry contact as required.
Procedure
Step 1 Clear associations between alarms and dry contact outputs or inputs. Use ALM1/
DIN1 as an example.
Table 12-15 Clearing associations between alarms and dry contact outputs
Main Menu
Parameters
Settings
Table 12-16 Clearing associations between alarms and dry contact inputs
Main Menu
Parameters
Settings
Step 2 Set alarm parameters for dry contacts.
Table 12-17 Setting alarm parameters for dry contacts
Main Menu
Second-Level
Menu
Parameters
UIM
Settings
Step 3 Set alarm actions for dry contact outputs or inputs. Use ALM1/DIN1 as an
example.
Issue 02 (2021-09-28)
Second-Level
Third-Level
Menu
Menu
Alarm
Clear ALM Asso.
Parameters
Second-Level
Third-Level
Menu
Menu
Alarm
Clear DI Asso.
Parameters
Third-Level Menu
DIN1/ALM1 Config
DIN2/ALM2 Config
DIN3/ALM3 Config
DIN5/ALM4 Config
DIN6/ALM5 Config
Copyright © Huawei Technologies Co., Ltd.
12 Power-on and Commissioning
Fourth-Level
Setting
Menu
Clear ALM1 Asso.
Yes
Fourth-Level
Setting
Menu
Clear DIN1 Asso.
Yes
Default Value
Setting
ALM
ALM, DIN
ALM
ALM, DIN
ALM
ALM, DIN
ALM
ALM, DIN
ALM
ALM, DIN
133