Huawei PowerCube 1000 Installation Manual page 134

Table of Contents

Advertisement

PowerCube 1000 (STC, Saudi Arabia, ICC800-A1-C2,
ESC800-A1)
Installation Guide
Procedure
Step 1 Set load disconnection parameters based on site requirements.
Table 12-7 Setting customized load disconnection parameters on the LCD
Main Menu
Second
-Level
Menu
Parameters
Digital
Settings
Power
Issue 02 (2021-09-28)
Time mode: When an AC power failure occurs, you can perform disconnection
management based on the power failure duration.
High-temperature power-off mode: You can perform disconnection
management based on the ambient temperature (reported by the ambient
temperature sensor).
Planned power-off mode: You can perform disconnection management based
on the preset time segment.
Exempt period without backup power: When an AC power failure occurs, you
can perform disconnection management within the specified period.
Third-Level
Fourth-
Menu
Level
Menu
DC Output
Branch
Distribut.
Usage
Config
Load
Branch
n
Copyright © Huawei Technologies Co., Ltd.
12 Power-on and Commissioning
Fifth-Level
Setting
Menu
Branch n
Customized
Usage Config
Load
Enb Load
Enable
Discon
Load Discon
Voltage
Mode
Mode
Load Discon
44.0 V
Volt
Load Recon
51.5 V
Volt
Load Discon
0.00 kWh
Power
Load Discon
15%
Cap
Load Discon
360 min
Time
Enb HTD
Disable
HTD Temp
65°C
Enb PD
Disable
PD Start Time
00:00:00
Value Range
-
Disable/Enable
Voltage Mode,
Capacity Mode,
Consumption
Mode, Time
Mode
36.0–56.0
37.0–58.0
0.00–65.00
0–99
0–1440
Disable/Enable
25.0–80.0
Disable/Enable
HH:MM:SS
126

Advertisement

Table of Contents
loading

Table of Contents