Figure 12- Set Digital Input Sensors Specified Time Period Before Causing A Trigger; Figure 13- Ip Device Settings - NTI ENVIROMUX Series Installation And Operation Manual

Remote power reboot switch with iec320 c13 outlet
Hide thumbs Also See for ENVIROMUX Series:
Table of Contents

Advertisement

NTI Power Remote Rebooter with C13 Connection
Digital Input sensors need to be in a new state for a specified amount of time before a trigger can occur. Click "Edit" to open
Sensor Settings page.

Figure 12- Set Digital Input sensors specified time period before causing a trigger

You can enter a custom description for the sensor connected to Digital In #1 and #2. You can also enter how long a state change
in the sensor must be stable, in milliseconds, before the sensor state will trigger the output. After making any changes, click
"Save".
An IP device can be configured to be pinged by the PWR-RMT-RBT-C13. Click "Edit" to open the IP Device Settings page. After
making any changes, click "Save".
IP Device Settings
Description
Description
Enter the name you would like to be applied to the IP device
Enable
Apply a checkmark if this IP device is to be enabled to effect the outputs
IP Address
Enter either the IP address or the URL of the IP device
Ping Period
Enter the amount of time in seconds between pings to the IP address
Timeout
Enter the time period in seconds to wait for a response to a ping (range is 1 - 255)

Figure 13- IP Device Settings

12