Comms > Dialler Reporting >

Burg Report Delay

(*** System Wide Parameter ***)
This menu programs how long the panel will delay reporting
Burglary alarm reports. Only burglary (non-fire) zones that have
been programmed for Delay Report in MENU 3-1-7 — Report
Option will follow the Burglary Report Delay time.
1)
Press [MENU] + [5] + [4] + [6]. The keypad will display the
current burglary report delay time.
Burg Report Delay
000 seconds
Press 0-9 OK to SAVE
Using the numeric keys, enter the new report delay time then
2)
press [OK] to save and exit or press [MENU] to exit without
saving. Valid entires are 0 to 255 seconds
Comms > Dialler Reporting >

Fire Report Delay

(*** System Wide Parameter ***)
This menu programs how long the panel will delay reporting fire
zone alarm reports. Only fire zones that have been programmed
for Delay Report in MENU 3-1-7 — Report Option will follow the
Fire Report Delay time.
1)
Press [MENU] + [5] + [4] + [7]. The keypad will display the
current Fire Report Delay time.
Fire Report Delay
000 seconds
Press 0-9 OK to SAVE
Using the numeric keys, enter the new report delay time then
2)
press [OK] to save and exit or press [MENU] to exit without
saving. Valid entires are 0 to 255 seconds.
CO MMS R EG IST R AT ION
Comms > Registration >

Customer

Reserved for future use.
9-12
Comms Programming
MENU 5-4-6
0
0
0
SECONDS
MENU 5-4-7
0
0
0
SECONDS
MENU 5-5-0
Comms > Registration >

Installer

Reserved for future use.
Comms > Comms Test >

Email Address

This menu allows the master user to program an email address
that the system will send email reports to. A maximum of 80
characters can be used to program the email address.
1)
Enter your Master PIN + [MENU].
2)
Enter [5] + [5] + [8] + [OK].
The keypad will display the current email address.
Email P001
_

Press

3)
Use the numeric, [0] to [9], [] and [] keys to enter or change
the email address as required.
At any time you can use the [] and [] keys to scroll
through the complete list of available characters.
To clear all characters from the cursor position to the
right, press the [OFF] key.
4)
When the email address is complete, press [OK] to save and exit,
or press [MENU] to exit without saving.
To stop email reporting simply remove the email
address or disable all of the email options in MENU
5-5-9.
i
When entering an email address the @ symbol is
represented
on
Note
To enter this character press the 1 key repeatedly until
the symbol appears in the display.
Comms > MyAlarm >

Email Options

1
Open / Close Reports
2
Zone Alarm Reports
3
Zone Trouble Reports
4
System Reports
5
Access Reports
6
Reserved
7
Reserved
8
Reserved
MENU 5-5-1
-
MENU 5-5-8
OK to SAVE
the
keypad
display
as
-
MENU 5-5-9