Zone Array; Testing The System; Basic Reporting Reference - Bosch Solution 16plus Installation Manual

Hide thumbs Also See for Solution 16plus:
Table of Contents

Advertisement

Solution 16
plus
Installation Manual

ZONE ARRAY

The feature allows you to view the condition of all zones on
the panel in banks of 16 zones at a time. From the installer
programing mode press MENU 3-0-1 to access the zone array.
Use the up and down arrow keys to scroll up and down the zone
banks and Press [OK] or [MENU] when finished.
The following information can be displayed depending on the
current zone status.
N= NORMAL
S = SHORTED
A= ALARM
T= TAMPER
- = DISABLED
0000000001111111
1234567890123456
NSA-ANAT--------
PRESS

, OK or MENU
In the above example screen,
N = Zone 01 and 06 are Normal (Sealed)
S = Zone 02 is Shorted
A = Zone 03,05,07 are in Alarm (Unsealed)
T = Zone 08 is in Tamper Alarm (Unsealed)
- = Zone 04, 09-16 are Disabled (Unused)
T ESTI NG THE SYST E M
You will need to be in programming mode before accessing the
test functions listed below.
Walk Test
Use the walk test command MENU 3-9-0 to test and verify that
all zones work correctly.
External Audible Test
Use MENU 4-9-0 to test and verify that all horn speakers operate.
This test will sound the horn speaker for two seconds.
Internal Audible Test
Use MENU 4-9-1 to test and verify that all 12 VDC sirens operate.
This test will sound the siren for two seconds.
Strobe Test
Use MENU 4-9-2 To test and verify that the strobe operates. This
test will turn on the strobe until you manually stop the test.
Battery Test
Use MENU 7-9-1 to test the back-up battery that is connected to
the control panel.
Communication Test
Use MENU 5-9-0 to test the telephone reporting capability of
the control panel. You can also activate a communication test
by holding down the Test / Mail key on the keypad.
4-4
Programming Overview
BASI C REPOR TI NG R EFERE NCE
The following table is a shortform point ID listing.
For a complete listing of all the CID and SIA event reporting
information that will be sent by the control panel you will need
to view the base station template document that is included on
the SolutionLink CD or contact your distributor.
Point ID Table
Ur999
Ur001 - 256
Ur000
Zn999
Zn998
Zn891-898
Zn881-888
Zn871-878
Zn861-868
Zn851-858
Zn841-848
Zn831-838
Zn821-828
Zn811-818
Zn801-808
Zn791-798
Zn001-128
Table 16: Shortform Point ID Listing
Module Description
Installer
Users
Quick Arm
Keyfob Low Battery
Keyfob Panic Alarm
Panels 1-8
Keypads 1-8
Ethernet 1-8
GSM 1-8
Output Expander 1-8
Serial Expander 1-8
Lan P/Supply 1-8
RF Reciever 1-8
Access 1-8
X10 1-8
Lift 1-8
Zones
Bosch Security Systems 05/10 BLCC100I