Bosch Solution 16plus Installation Manual page 104

Hide thumbs Also See for Solution 16plus:
Table of Contents

Advertisement

Solution 16
plus
Installation Manual
Arming Allowed On Low Battery
Setting this option will allow the system to be armed even though the
panel currently has a low battery condition.
When this option is disabled, the panel will not arm if there is a low
battery condition or if the battery is missing. The user will be notified
of the system trouble on the keypad and they will need to have the
fault rectified before the system or area can be armed.
i
Software Version 1.07 and higher now allows a schedule to
automatically turn on an area (or multiple areas) irrespective on
how this option is programmed. In previous software versions,
Note
if this option was disabled, a schedule would not automatically
turn on an area if a low or missing battery condition was present
and this option was turned off.
System > Power >
Fuse Options
1
Display COMM+ Current Overload Condition
2
Report COMM+ Current Overload Condition
3
Display +12V (Accessories) Current Overload Condition
4
Report +12V (Accessories) Current Overload Condition
5
Display LAN+ Overload Condition
6
Report LAN+ Overload Condition
7
Reserved
8
Reserved
This menu option allows you to configure the Fuse related
system options.
(*** System Wide Parameter ***)
1)
Press [MENU] + [7] + [3] + [2]. The keypad will display the
current Fuse Options.
 Display COMM+ O/Load
 Report COMM+ O/Load
 Display +12V O/Load
Press  OK ON OFF MENU
Use the up and down arrow keys to highlight the option then
2)
press the [ON] key to enable or the [OFF] key to disable.
3)
Repeat Step 2 until all options are programmed as required,
then press [OK] to save and exit or press [MENU] to exit
without saving.
Display COMM + Current Overload
Setting this option allows the keypad to display a system trouble
message when the current load on the COMM + terminal exceeds its
maximum rating of 3 Amps.
Report COMM + Current Overload
Setting this option will cause the panel to send an Overcurrent
Trouble report to the base station when the current load on the
COMM + terminal exceeds its maximum rating of 3 Amps.
Display +12V (Accessories) Current Overload
Setting this option allows the keypad to display a system trouble
message when the current load on the +12 V terminal exceeds its
maximum rating of 1Amp.
Report +12V (Accessories) Current Overload
11-8
System Programming
MENU 7-3-2
Y
Y
Y
Y
Y
Y
N
N
Setting this option will cause the panel to send an Overcurrent
Trouble report to the base station when the current load on the +12 V
terminal exceeds its maximum rating of 1Amp.
Display LAN + Current Overload
Setting this option allows the keypad to display a system trouble
message when the current load on the LAN+ terminal exceeds its
maximum rating of 1Amp.
Report LAN + Current Overload
Setting this option will cause the panel to send an Overcurrent
Trouble report to the base station when the current load on the LAN+
terminal exceeds its maximum rating of 1Amp.
HOR N SPEAKER OPTIONS
System > Siren >
Tone
This menu allows you to customise the tone that is emitted
from the horn speaker when a non-fire alarm is triggered. By
changing the tone and speed, it is possible to program a unique
siren sound for each system when you are installing a number
of them in close proximity to each other.
1)
Press [MENU] + [7] + [4] + [0]. The keypad will display the
current siren tone.
Tone
1. . . . . . . . . . . . . 7
-------------  ---------
Press  OK to SAVE
Use the up and down arrow keys to change the the siren tone.
2)
To test the new siren tone press [ON] to sound the siren and
3)
press [OFF] to turn the siren off.
4)
Repeat Steps 2 and 3 until the desired siren tone is achieved
then press [OK] to save and exit, or press [MENU] to exit
without saving.
i
Only outputs programmed as Event Type 46 and or 47 will be
affected by this menu option.
Note
System > Siren >
Speed
This menu allows you to customise the speed of the siren tone
when a non-fire alarm is triggered. By changing the tone and
speed, it is possible to program a unique siren sound for each
system when you are installing a number of them in close
proximity to each other.
1)
Press [MENU] + [7] + [4] + [1]. The keypad will display the
current siren speed.
Speed
S. . . . . . . . . . . . . F
-------------  ---------
Press  OK to SAVE
MENU 7-4-0
MENU 7-4-1
Bosch Security Systems 05/10 BLCC100I

Advertisement

Table of Contents
loading

Table of Contents