External Protective Grounding Requirements; Connection Procedure - Sungrow SG25CX-P2 User Manual

Pv grid-connected inverter
Hide thumbs Also See for SG25CX-P2:
Table of Contents

Advertisement

5 Electrical Connection
The external protective grounding terminal must meet at least one of the following
requirements.
The cross-sectional area of the grounding cable is not less than 10 mm
per wire or 16 mm
protective grounding terminal and the AC side grounding terminal be reliably
grounded.
If the cross-sectional area of the grounding cable is less than 10 mm
wire or 16 mm
grounding terminal and the AC side grounding terminal are reliably grounded.
The grounding connection can be made by other means if they are in accordance
with the local standards and regulations, and SUNGROW shall not be held liable
for the possible consequences.

5.5.1 External Protective Grounding Requirements

All non-current carrying metal parts and device enclosures in the PV power system should
be grounded, for example, brackets of PV modules and inverter enclosure.
When there is only one inverter in the PV system, connect the external protective grounding
cable to a nearby grounding point.
When there are multiple inverters in the PV system, connect the external protective ground-
ing terminals of all inverters and the grounding points of the PV module brackets to ensure
equipotential connections to ground cables (according to the onsite conditions).

5.5.2 Connection Procedure

Step 1 Prepare the cable and OT/DT terminal, refer to
Step 2 Remove the screw on the grounding terminal and fasten the cable with a screwdriver.
40
2
for aluminum wire. It is recommended that both the external
2
for aluminum wire, ensure that both the external protective
" Crimp OT/DT
terminal".
User Manual
2
for cop-
2
for copper