4 Mechanical Mounting
•
It is strictly prohibited to install the inverter in environments with vibration and strong elec-
tromagnetic field. Strong-magnetic-field environments refer to places where magnetic
field strength measures over 30A/m.
•
The inverter generates noise during operation and is not recommended to be installed in
living areas.
4.2.2 Carrier Requirements
The mounting structure where the inverter is installed must comply with local/national stand-
ards and guidelines. Ensure that the installation surface is solid enough to bear four times
the weight of the inverter and is suitable for the dimensions of the inverter (e.g. cement walls,
plasterboard walls, etc.).
The structure should meet the following requirements:
4.2.3 Angle Requirements
Install the inverter vertically or at the maximum allowable rear tilt angle. Do not install the in-
verter horizontally, forward, excessively backward, sideways, or upside down.
Inverters in floating plants cannot be installed at a back tilt.
20
User Manual