Instructions Concerning Connection Cables; Master Module Mosaic M1 - Reer MOSAIC M1 Installation And Use Manual

Modular safety integrated controller
Hide thumbs Also See for MOSAIC M1:
Table of Contents

Advertisement

Instructions concerning connection cables

Wire size range: AWG 12÷30, (solid/stranded) (UL).
Use 60/75°C copper (Cu) conductor only.
We recommend the use of separate power supplies for the safety module and for other electrical
power equipment (electric motors, inverters, frequency converters) or other sources of
disturbance.
Cables used for connections of longer than 50m must have a cross-section of at least 1mm 2
(AWG16).
Connections of each single MOSAIC system unit are listed in the table below:

Master Module MOSAIC M1

TERMINAL
SIGNAL
1
24VDC
2
MASTER_ENABLE1
3
MASTER_ENABLE2
4
0VDC
5
OSSD1_A
6
OSSD1_B
7
RESTART_FBK1
8
OUT_STATUS1
9
OSSD2_A
10
OSSD2_B
11
RESTART_FBK2
12
OUT_STATUS2
13
OUT_TEST1
14
OUT_TEST2
15
OUT_TEST3
16
OUT_TEST4
17
INPUT1
18
INPUT2
19
INPUT3
20
INPUT4
21
INPUT5
22
INPUT6
23
INPUT7
24
INPUT8
20
TYPE
DESCRIPTION
-
24VDC power supply
Input
Master Enable 1
Input
Master Enable 2
-
0VDC power supply
Output
Static output 1
Output
Input
Feedback/Restart 1
Output
SIL 1/PL c
Output
Static output 2
Output
Input
Feedback/Restart 2
SIL 1/PL c
Output
Output
Short circuit detection output
Output
Short circuit detection output
Output
Short circuit detection output
Output
Short circuit detection output
Input
Digital input 1
Input
Digital input 2
Input
Digital input 3
Input
Digital input 4
Input
Digital input 5
Input
Digital input 6
Input
Digital input 7
Input
Digital input 8
Table 2
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
Input ("type B" according to
Input ("type B" according to
Input according to EN 61131-2
output
Input according to EN 61131-2
output
Input according to EN 61131-2
Input according to EN 61131-2
Input according to EN 61131-2
Input according to EN 61131-2
Input according to EN 61131-2
Input according to EN 61131-2
Input according to EN 61131-2
Input according to EN 61131-2
8540780 • 25/01/2023 • Rev.43
OPERATION
-
EN 61131-2 )
EN 61131-2 )
-
PNP active high
PNP active high
PNP active high
PNP active high
PNP active high
PNP active high
PNP active high
PNP active high
PNP active high
PNP active high

Advertisement

Table of Contents
loading