Reer MOSAIC M1 Installation And Use Manual page 44

Modular safety integrated controller
Hide thumbs Also See for MOSAIC M1:
Table of Contents

Advertisement

Different
output
can be set:
• 4 single channels (1 Safety Output per channel with its relative feedback input).
• 2 dual channels (2 Safety Outputs per channel with their relative feedback input).
• 1 dual channel and 2 single channels.
Using single channels OSSD, to maintain Safety Integrity Level (SIL) "3" requirements the OSSD
outputs must be independent.
Common cause failures between OSSD outputs must be excluded by observing an appropriate
cable installation (i.e. separate cable paths).
External devices cannot be connected to the outputs unless explicitly planned in the MSD
program configuration.
Configuration with 2 dual channel
outputs (safety category SIL3/Pl e)
44
configurations
(configurable
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
with
MSD
configuration
Configuration with 4 single outputs
(safety category SIL3/Pl e)
8540780 • 25/01/2023 • Rev.43
software)