Parameters
Output Type: There is a choice of 2 different output type:
Single Output Type
Double Output Type
Using MOSAIC M1S, MOSAIC M1S COM, MI8O4, MO4L, MO4LHCS8 modules, the operator can
choose between different configurations:
1. Four SINGLE OUTPUTS function blocks (single output type)
2. Two SINGLE OUTPUTS function blocks (double output type)
3. Two SINGLE OUTPUTS function blocks (single output type) + one SINGLE OUTPUTS function
block (double output type)
Using single channels OSSD, to maintain Safety Integrity Level (SIL) "3" requirements the OSSD
outputs must be independent.
Common cause failures between OSSD outputs must be excluded by observing an appropriate
cable installation (i.e. separate cable paths).
Example of project - 2 single output type function blocks + 1 double output type function blocks
Here below you can find the explanation of the MOSAIC M1S, MOSAIC M1S COM, MI8O4, MO4L,
MO4LHCS8 SINGLE-OSSD configurations.
Manual Reset: If selected this enables the request to reset each time the input signal falls. Otherwise,
output enabling directly follows In input conditions.