MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
"With occupied
sensors" selected
X
-
Timeout (sec): Used to set the time, between 10 sec and infinity, by which the Override
function must end.
Override mode: Used to configure the type of Override (pulsed or maintained action).
With OverOut: Used to activate an Override active Signaling output (active when high).
With Request: Used to activate a Signaling output (active when high) indicating that the
Override function can be activated.
Manual Reset:
•
Should the INPUT be active (TRUE), the reset enables the output of the function block.
•
Should the INPUT be not active (FALSE), the output of the function block follows the
OVERRIDE request.
There are two types of reset: Manual and Monitored. When Manual is selected the system
only verifies the signal's transition from 0 to 1. If Monitored is selected the double transition
from 0 to 1 and then back to 0 is verified.
8540780 • 25/01/2023 • Rev.43
Light
Occupied
curtain
sensor
occupied
X
-
-
X
X
-
X
X
t = 250 ms
Override
Input
request
0
1
0
1
0
1
0
1
5s > t1 > 250 ms
t2 = 250 ms
Override
output
1
1
1
1
235