INSTRUCTIONS CONCERNING CONNECTION CABLES.

Wire size range: AWG 12÷30, (solid/stranded) (UL).
Use 60/75°C copper (Cu) conductor only.
We recommend the use of separate power supplies for the safety
module and for other electrical power equipment (electric motors,
inverters, frequency converters) or other sources of disturbance.
Cables used for connections of longer than 50m must have a cross-
section of at least 1mm2 (AWG16).
TERMINAL
SIGNAL
1
24VDC
2
MASTER_ENABLE1 Input
3
MASTER_ENABLE2 Input
4
0VDC
5
OSSD1_A
6
OSSD1_B
7
RESTART_FBK1
8
OUT_STATUS1
9
OSSD2_A
10
OSSD2_B
11
RESTART_FBK2
12
OUT_STATUS2
13
OUT_TEST1
14
OUT_TEST2
15
OUT_TEST3
16
OUT_TEST4
17
INPUT1
18
INPUT2
19
INPUT3
20
INPUT4
21
INPUT5
22
INPUT6
23
INPUT7
24
INPUT8
8540797 02 • 18/03/2021 • Rev.1
MOSAIC M1 - MASTER MODULE
M1 module
TYPE
DESCRIPTION
-
24VDC power supply
Master Enable 1
Master Enable 2
-
0VDC power supply
Output
Static output 1
Output
Input
Feedback/Restart 1
Programmable
Output
digital output
Output
Static output 2
Output
Input
Feedback/Restart 2
Programmable
Output
digital output
Short circuit
Output
detected output
Short circuit
Output
detected output
Short circuit
Output
detected output
Short circuit
Output
detected output
Input
Digital input 1
Input
Digital input 2
Input
Digital input 3
Input
Digital input 4
Input
Digital input 5
Input
Digital input 6
Input
Digital input 7
Input
Digital input 8
OPERATION
-
Input ("type B" according to
EN 61131-2 )
Input ("type B" according to
EN 61131-2 )
-
PNP active high
PNP active high
Input according to EN 61131-2
PNP active high
PNP active high
PNP active high
Input according to EN 61131-2
PNP active high
PNP active high
PNP active high
PNP active high
PNP active high
Input according to EN 61131-2
Input according to EN 61131-2
Input according to EN 61131-2
Input according to EN 61131-2
Input according to EN 61131-2
Input according to EN 61131-2
Input according to EN 61131-2
Input according to EN 61131-2
13