Reer MOSAIC M1 Installation And Use Manual page 202

Modular safety integrated controller
Hide thumbs Also See for MOSAIC M1:
Table of Contents

Advertisement

Signal comparison
Signal comparison: Selecting this item will
allow the DIGITAL COMPARATOR operator
to
compare
the
(In1_A...In4_A) with the second four B
inputs (In1_B...In4_B).
Depending on the value of the inputs and
the operation selected, the following results
will be obtained:
< (Lower):
1 (TRUE) as long as the value of A
inputs is lower than the value of B inputs. The OUT output will be set to 0 (FALSE)
when the value of A inputs is higher than or equal to the value of B inputs.
>= (Higher or equal): The OUT output will be 1 (TRUE) as long as the value of A
inputs is higher than or equal to the value of B inputs. The OUT output will be set to
0 (FALSE) when the value of A inputs is lower than the value of B inputs.
> (Higher):
higher than the value of B inputs. The OUT output will be set to 0 (FALSE) when the
value of A inputs is lower than or equal to the value of B inputs.
<= (Lower or equal): The OUT output will be 1 (TRUE) as long as the value of A inputs
is lower than or equal to the value of B inputs. The OUT output will be set to 0 (FALSE)
when the value of A inputs is higher than the value of B inputs.
= (Equal): The OUT output will be 1 (TRUE) as long as the value of A inputs is equal
to the value of B inputs. The OUT output will be set to 0 (FALSE) when the value of A
inputs is different from the value of B inputs.
!= (Different): The OUT output will be 1 (TRUE) as long as the value of A inputs is
different from the value of B inputs. The OUT output will be set to 0 (FALSE) when
the value of A inputs is equal to the value of B inputs.
202
first
four
A
inputs
The OUT output will be
The OUT output will be 1 (TRUE) as long as the value of A inputs is
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
8540780 • 25/01/2023 • Rev.43