MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
t = 250ms
External K time monitoring: If selected, enables the setting of the time window within which the
external feedback signal is to be monitored (according to following output conditions).
OUTPUT
1
0
With high level (TRUE) OUTPUT, the FBK signal must be at low level (FALSE) within the set time.
Otherwise, OUTPUT is set to low level (FALSE) and the error is indicated on the master MOSAIC M1
by the flashing CLEAR LED corresponding to the OSSD in error.
Enable Error Out: If selected, enables the ERROR OUT output. This output is set to high level
(TRUE) when an external FBK error is detected.
The Error Out signal is reset in case of one of the following events:
1. Switching on and switching off of system.
2. Activation of the RESET MOSAIC M1 operator.
Example of OSSD with correct Feedback signal:
In this case ERROR OUT=FALSE
OSSD feedback unconnected: If selected, the feedback must not be connected. If not selected the
feedback must be connected directly to 24V or through the series of NC contacts of K1/K2.
This parameter is only applicable to module MO4LHCS8 firmware version >0.1
8540780 • 25/01/2023 • Rev.43
5s > t1 > 250ms
t2 = 250ms
MOSAIC M1, MOSAIC M1S, MOSAIC M1S COM
FBK
ERROR
0
0
1
1
There are two types of reset: Manual and
Monitored. In selecting the Manual
option only signal transition from 0 to 1
is verified. If the Monitored option is
selected, the double transition from 0 to
1 and back to 0 is verified.
Enable Status: If selected, enables the
connection of the current OSSD state to
any point on the schematic.
CLEAR LED
0
Flashing
Example of OSSD with incorrect Feedback signal
(k external time exceeded):
In this case ERROR OUT=TRUE
135