Siemens SIMATIC ET 200AL System Manual page 514

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200AL:
Table of Contents

Advertisement

Representation of analog values
B.4 Representation of analog values for resistance thermometer
Table B- 7
Resistance thermometer Ni 100 climatic
Ni x00 climatic in °C
Values
(1 digit = 0.01 °C)
Dec.
>155.00
32767
155.00
15500
:
:
130.01
13001
130.00
13000
:
:
-60.00
-6000
-60.01
-6001
:
:
-105.00
-10500
<-105.00
-32768
44
Ni x00 climatic in °F
(1 digit = 0.01 °F)
Hex.
7FFF
>311.00
3C8C
311.00
:
:
32C9
266.01
32C8
266.00
:
:
E890
-76.00
E88F
-76.01
:
:
D6FC
-157.00
8000
<-157.00
Analog input module AI 4xU/I/RTD 4xM12 (6ES7144-5KD00-0BA0)
Values
Dec.
Hex.
32767
7FFF
31100
797C
:
:
26601
67E9
26600
67E8
:
:
-7600
E250
-7601
E24F
:
:
-15700
C2AC
-32768
8000