Siemens SIMATIC ET 200AL System Manual page 512

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200AL:
Table of Contents

Advertisement

Representation of analog values
B.3 Representation of analog values for resistance-based sensors
B.3
Representation of analog values for resistance-based sensors
Resistance-based sensor
Table B- 3
Resistance-based sensor of 150 Ω and 300 Ω
Values
Dec.
Hex.
32767
7FFF
32511
7EFF
27649
6C01
27648
6C00
20736
5100
1
1
0
0
-1
FFFF
:
:
-4864
ED00
-32768
8000
If the sensors are not connected correctly
1
B.4
Representation of analog values for resistance thermometer
Table B- 4
Resistance thermometer Pt 100 standard
Pt x00
Values
standard
Dec.
Hex.
in °C
(1 digit =
0.1°C)
>1000.0
32767
7FFF
1000.0
10000
2710
:
:
:
850.1
8501
2135
850.0
8500
2134
:
:
:
-200.0
-2000
F830
-200.1
-2001
F82F
:
:
:
-243.0
-2430
F682
<-243.0
-32768
8000
42
Resistance-based sensor range
150 Ω
>176.38 Ω
176.38 Ω
150 Ω
112.5 Ω
5.43 mΩ
0 Ω
(negative values are physically impossible)
Pt x00
Values
standard
Dec.
Hex.
in °F
(1 digit =
0.1 °F)
>1832.0
32767
7FFF
1832.0
18320
4790
:
:
:
1562.1
15621
3D05
1562.0
15620
3D04
:
:
:
-328.0
-3280
F330
-328.1
-3281
F32F
:
:
:
-405.4
-4054
F02A
<-405.4
-32768
8000
300 Ω
>352.77 Ω
352.77 Ω
300 Ω
225 Ω
10.85 mΩ
0 Ω
Pt x00
Values
standard
Dec.
in K
(1 digit =
0.1 K)
>1273.2
32767
1273.2
12732
:
:
1123.3
11233
1123.2
11232
:
:
73.2
732
73.1
731
:
:
30.2
302
<30.2
32768
Analog input module AI 4xU/I/RTD 4xM12 (6ES7144-5KD00-0BA0)
Range
Overflow
Overrange
Nominal range
Underrange
1
Underflow
1
Range
Hex.
7FFF
Overflow
31BC
Overrange
:
2BE1
2BE0
Nominal range
:
2DC
2DB
Underrange
:
12E
8000
Underflow
Manual, 03/2016, A5E32350124-AC

Advertisement

Table of Contents
loading

Table of Contents