Open User Communication
6.3 Instructions for Open User Communication
This FAQ (https://support.industry.siemens.com/cs/ww/en/view/58875807) describes how to
program the TCON instruction to set up a connection for Open User Communication
between two S7-1500 CPUs.
Protocols, system data types and employable instructions for programmed setup
The following table shows the protocols of the Open User Communication and the matching
system data types and instructions.
Table 6- 3
Protocol
TCP
ISO-on-TCP
ISO according to
ISO/IEC 8073 (Class
4)
UDP
FDL
Modbus TCP
E-mail
FTP
This protocol can only be used with the CM 1542-5
1
This protocol can only be used with the CP 1543-1
2
User-defined data type
3
70
Instructions for programmed setup of the connection
System data type
TCON_QDN
TCON_IP_v4
TCON_IP_RFC
TCON_ISOnative
TCON_Configured
TCON_IP_v4
TADDR_Param
TADDR_SEND_QDN
TADDR_RCV_IP
1
TCON_FDL
TCON_IP_v4
TCON_QDN
TMAIL_v4
TMAIL_v6
TMAIL_FQDN
2
FTP_CONNECT_IPV4
FTP_CONNECT_IPV6
FTP_CONNECT_NAME
Instructions
Establish connection and send/receive data
via:
TSEND_C/TRCV_C or
TCON, TSEND/TRCV or
1
TCON, TUSEND/TURCV
(connection can be terminated via
TDISCON)
Establish connection and send/receive data
via:
TSEND_C/TRCV_C
TUSEND/TURCV/TRCV
(connection can be terminated via
TDISCON)
Establish connection and send/receive data
via:
TSEND_C/TRCV_C or
TCON, TSEND/TRCV or
TCON, TUSEND/TURCV
(connection can be terminated via
TDISCON)
MB_CLIENT
MB_SERVER
TMAIL_C
FTP_CMD
3
3
3
Function Manual, 12/2017, A5E03735815-AF