Technical specifications
Technical specifications of the interface module IM 157-1 DP
General information
Product type designation
Hardware functional status
Firmware version
Vendor identifier (VendorID)
Product function
I&M data
Engineering with
STEP 7 TIA Portal can be configured/integrated
as of version
STEP 7 can be configured/integrated as of version V5.5 SP4 Hotfix 3 or higher
PROFIBUS as of GSD version/GSD revision
Configuration control
Via data record
Supply voltage
Load voltage 1L+
Rated value (DC)
Low limit of permitted range (DC)
High limit of permitted range (DC)
Reverse polarity protection
Input current
Current consumption (rated value)
From load voltage 1L+ (unswitched current)
From load voltage 2L+, max.
Power loss
Power loss, typ.
Address area
Address space per station
Address space per station, max.
Interfaces
Number of PROFIBUS interfaces
1st interface
Interface type
42
6ES7157-1AA00-0AB0
IM 157-1 DP
E01
V1.0.x
81A9H
Yes; I&M0 to I&M3
as of STEP 7 V13 SP1
GSD as of revision 5
Yes
24 V
20.4 V
28.8 V
Yes; against destruction
50 mA
4 A; maximum value
4 A; maximum value
1.7 W
244 bytes
1
PROFIBUS DP
Interface module IM 157-1 DP (6ES7157-1AA00-0AB0)
Manual, 12/2016, A5E32100641-AD