Digital inputs
Number of inputs
Input characteristic curve acc. to IEC 61131,
type 3
Number of inputs that can be controlled simulta-
neously
All mounting positions
•
Input voltage
Type of input voltage
Rated value (DC)
For signal "0"
For signal "1"
Input current
For signal "1", typ.
Input delay (for rated value of input voltage)
For standard inputs
•
•
•
•
Cable length
Unshielded, max.
Digital outputs
Number of outputs
•
Short-circuit protection
•
Limitation of inductive shutdown voltage to
Switching capacity of outputs
With lamp load, max.
Load resistance range
Low limit
High limit
Output voltage
For signal "1", min.
Output current
For signal "1" rated value
For signal "0" residual current, max.
Digital input/digital output module DIQ 4+DQ 4x24VDC/0.5A 8xM8 (6ES7143-5BF00-0BA0)
Manual, 02/2016, A5E3234988-AC
up to 55 °C, max.
at "0" to "1", min.
at "0" to "1", max.
at "1" to "0", min.
at "1" to "0", max.
In groups of
Response threshold, typ.
Technical specifications
6ES7143-5BF00-0BA0
4; can be configured as DIQ
Yes
4
DC
24 V
-3 ... +5 V
+11 ... +30 V
3.2 mA
1.2 ms
4.8 ms
1.2 ms
4.8 ms
30 m
8; 4 DQ fixed, 4 DIQ can be assigned
4; 2 load groups for 4 outputs each
Yes; per channel, electronic
0.7 A
2L+ (-47 V)
5 W
48 Ω
4 kΩ
L+ (-0.8 V)
0.5 A
0.5 mA
23