Siemens SIMATIC ET 200AL System Manual page 380

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200AL:
Table of Contents

Advertisement

Configuration modes for digital inputs/outputs
3.3 Parameters/address space
3.3
Parameters/address space
3.3.1
Parameters
The following table shows the parameters for the DIQ 16x24VDC/0.5A 8xM12 digital input /
digital output module in the configuration modes for digital inputs and outputs.
Table 3- 6
Parameters
Diagnostics: Missing load voltage
2L+
Diagnostics: Short-circuit to ground
Reaction to CPU/master STOP
Freely configurable channel*
Substitute value channel
Input delay**
* = Can only be set in DIQ or DIQ with value status configuration mode.
** = Not available in DQ16 mode. Only values starting from 1.6 ms can be configured for the input
delay for channels 8..15.
20
Parameters
Digital input/Digital output module DIQ 16x24VDC/0.5A 8xM12 (6ES7143-5AH00-0BA0)
Value range
Default
Disable
Disable
Enable
Disable
Disable
Enable
Shut down
Shut down
Keep last value
Output substi-
tute value
DI
DI
DQ
0
0
1
3.2 ms
0.05 ms
0.1 ms
0.4 ms
0.8 ms
1.6 ms
3.2 ms
12.8 ms
20 ms
Scope
Module
Module
(Short-circuit of
encoder supply or
of the output to
ground)
Module
(digital outputs)
Channel
Channel
(digital outputs)
Channel
(Digital inputs)
Manual, 09/2017, A5E38688112-AB