Siemens SIMATIC ET 200AL System Manual page 267

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200AL:
Table of Contents

Advertisement

Parameters/address space
4.1
Parameters
The table below shows the parameters for the DI 8x24VDC 4xM12 digital input module.
Table 4- 1
Parameters
Diagnostics: Short-circuit to ground
4.2
Explanation of the parameters
Diagnostics: Short-circuit to ground
Enabling of the diagnostics if a short-circuit of the encoder supply to ground occurs.
4.3
Address space
The figure below shows the assignment of the address space for the digital input module
DI 8x24VDC 4xM12 with value status (Quality Information, QI).
The address space for the value status is allocated by the module, if the value status is
configured using the PROFINET interface module.
Image 4-1
Configuration options of the DI 8x24VDC 4xM12 digital input module
You have the following configuration options:
● Configuration 1: without value status
● Configuration 2: with value status
Evaluating the value status
An additional byte is occupied in the input address space if you enable the value status for
the digital input module. Bits 0 to 7 in this byte are assigned to a channel and return
information about the validity of the digital input value.
Bit = 1: No error on channel.
Bit = 0: Error on channel.
16
Parameters
Address space
Value range
Default
Disable
Disable
Enable
Digital input module DI 8x24VDC 4xM12 (6ES7141-5AF00-0BA0)
4
Scope
Module
Manual, 02/2016, A5E36680963-AA