Siemens SIMATIC ET 200AL System Manual page 104

Distributed i/o system
Hide thumbs Also See for SIMATIC ET 200AL:
Table of Contents

Advertisement

Accessories/spare parts
C.2 Cables
C.2
Cables
Cables for ET-Connection standard and PUR cable
The cables for ET-Connection are available in the following versions and lengths:
● Bus cable (4-wire), pre-assembled on both sides with 2 M8 connectors, 4-pole, shielded
– available lengths: 0.19 m, 0.3 m, 1 m, 2 m, 5 m, 10 m, 15 m
● Bus cable (4-wire), pre-assembled on both sides with 2 M8 connectors, angled, 4-pole,
shielded
– available lengths: 0.3 m, 1 m, 2 m, 5 m, 10 m, 15 m
● Bus cable (4-wire), pre-assembled on one side 1x M8 connector, 4-pole, shielded
– available lengths: 2 m, 5 m, 10 m, 15 m
The following table shows the technical properties of the bus cable ET-Connection standard.
Table C- 8
General information
Product type designation
Function
Degree of protection and protection class
IP65
IP67
Ambient conditions
Ambient temperature during mounting
minimum
maximum
Storage/transport temperature
Ambient temperature during transport and storage
minimum
maximum
Cables
Cable designation
Number of electrical wires
Design of shielding
Outside diameter of the inner conductor
Outside diameter of the wire insulation
Outside diameter of the cable sheath
Number of bending cycles
Permissible bending radius
102
Cables for ET-Connection
BUS CABLE ET-CONNECTION
To connect ET-CONNECTION devices with de-
gree of protection IP65/IP67
Yes
Yes
-30 °C
80 °C
-40 °C
80 °C
2Y(ST)CY 1x4x0.5/1.0-100-GN
4
Overlapped aluminum-lined sheet, coated with
shielding made of tin plated copper wires
0.5 mm
1.0 mm
5 mm
1000000; Trailing-chain suitable for 1 million
bending cycles with a bending radius of 100 mm,
a velocity of 4 m/s and an acceleration of 4 m/s²
System Manual, 02/2018, A5E31861578-AF