Response of the analog input module
Requirement
You can use the PROFIenergy function when you use the internal encoder supply.
Display
The channel status LEDs are not affected by PROFIenergy.
Response to error detection
All channels that are in pause mode on "PE_MODE_PROCEED" report their diagnostic
status as in productive mode.
The following applies for all channels which switch to a different pause mode:
● Encoder supply switch-off upon the start of "pause" does not result in the alarm "Wire
break".
● "Wire break", "Short circuit", "High limit violated" and "Low limit violated" error detection is
not possible during the "pause":
– Alarms for errors already pending before the "pause" are retained.
– After the "pause" is over, the error status is updated and incoming/outgoing errors are
● Hardware interrupts are not signaled.
Mode parameter
The following table shows the "Mode" parameter.
Table 7- 1
Element
Mode
Encoder supply U
1
deactivated in these measurement types.
Analog input module AI 4xU/I/RTD 4xM12 (6ES7144-5KD00-0BA0)
Manual, 03/2016, A5E32350124-AC
reported correspondingly.
Mode parameter
Code
0
: PE_MODE_PROCEED
D
1
: PE_MODE_SHUTDOWN
D
3
: PE_MODE_LAST_VALUE
D
4
: PE_MODE_SUBST_VALUE
D
is only provided for measurement type current and voltage and can only be
S
7.2 Response of the analog input module
Explanation
Proceed at "pause"
Value status "GOOD"
Switch off at "pause"
Encoder supply U
switched off
S
Pause substitute value: 7FFF
Value status "BAD"
Last value at "pause"
Encoder supply U
switched off
S
Pause substitute value: Last input value
Value status "BAD"
Substitute value at "pause"
Encoder supply U
switched off
S
Pause substitute value: Configured pause
substitute value
Value status "BAD"