Setting and determining system diagnostics
4.2 Options for displaying system diagnostics
Subordinate "Alarm display" tab
System diagnostics alarms are output in the "Alarm display" tab.
Figure 4-12
"Alarm display" tab
To receive alarms in STEP 7, follow these steps:
1. Open the project view.
2. Select the required CPU in the project tree.
3. To connect online with the respective CPU, select the shortcut menu command "Go
online".
4. Select the required CPU once again in the project tree and select the shortcut menu
command "Receive alarms".
Figure 4-13
5. Alarms are now displayed in the alarm display. "Archive view" is enabled by default.
6. To display the latest alarms, click the "Active alarms" icon
42
Receive alarms
.
Function Manual, 09/2016, A5E03735838-AD
Diagnostics