Parameter assignment/addressing
3.2 Device name and IP address
3.2.3

Assigning a device name and IP address

Assigning an IP address and subnet mask for an IO controller for the first time
You have the following options:
● Using a programming device or PC:
Connect your programming device/PC to the same network as the relevant PROFINET
device. The interface of the programming device/PC must be set to TCP/IP mode. During
the download, first of all display all available devices via the "Accessible devices"
download dialog box. Select the target device via its MAC address and then assign its
IP address before you download the hardware configuration including the configured
IP address (IP address is saved retentively).
● Using the display of a S7-1500 CPU:
The S7-1500 CPUs have a front cover with a display and operating keys. You can use
this display to assign or change the IP address. To set the IP address, navigate on the
display via the menu items "Settings" > "Addresses" > "X1 (IE/PN)" > "Parameters".
● Using a memory card:
If your PROFINET device is equipped for a memory card (Micro Memory Card/SIMATIC
memory card), plug this into your programming device/PC and save the hardware
configuration together with the configured IP address on this memory card. Then plug the
memory card into the PROFINET device. Once inserted, the PROFINET device
automatically applies the IP address.
If you have saved a configuration to the memory card with the "IP address is set directly
at the device" option, you must assign the IP address using a different method after
inserting the memory card (see section Permitting changes to the device name and IP
address directly on the device (Page 60)).
Assigning device names and IP address for "Device replacement without exchangeable
medium/programming device"
For devices without exchangeable medium (e.g., ET 200MP, ET 200SP) and devices that
support "Device replacement without exchangeable medium/PG" (e.g., ET 200S), the IO
controller can identify the device without name from the neighbor relationships specified by
the set topology and from actual neighbor relationships determined by the real PROFINET
devices. The IO controller then assigns the PROFINET device the configured name and
incorporates the PROFINET device in the user data traffic. (See also Device replacement
without exchangeable medium (Page 210)).
52
PROFINET with STEP 7 V15
Function Manual, 12/2017, A5E03444486-AH