PROFOX actuators
4.2.4.

Torque switching

Function
Table 32:
ID
Indication
PRM_578
End position CLOSED
PRM_9
End position OPEN
Limit
The actuator switches off once the set end positions (OPEN/CLOSED) have been
reached.
When switching off in end position, the overrun of the actuator must always be
accounted for. Overrun [1] is the travel from switching off until complete standstill.
The overrun of PROFOX actuators is relatively low thanks to the fact that it is a
variable speed actuator.
Figure 5: Limit seating
P
Tripping position
[1]
Overrun
Torque
The actuator switches off in the end position via torque seating.
For this, the torque switching has to be set to the tripping torque specified by the
valve manufacturer. When reaching the end position, the torque increases within the
valve seat. Once the set torque is reached, the actuator switches off.
Overload protection of the valve across the overall travel
Tripping in end positions (for PRM_578 End position CLOSED or PRM_9 End
position OPEN = Torque)
Setting as desired in Newtonmetre Nm or in Pounds per foot ft-lb
DIS_53 Configuration
DIS_13 Torque switching
Table 33:
ID
Indication
DIS_88
Tripping torque CLOSE
DIS_89
Tripping torque OPEN
PRM_5717
Operation mode in direction OPEN
PRM_5722
Operation mode in direction CLOSE
PRM_5716
Effective distance or end position zone
PRM_5718
Peak torque
PRM_5720
Behaviour in emergency operation
PRM_5403
Torque delay
PRM_5404
Torque delay time
The parameters for torque delay are only visible if the torque delay function (parameter
PRM_5403 Torque delay) is activated. For enabling and activation of functions, refer
to chapter Application functions.
Description
Type of seating in end position CLOSED
Type of seating in end position OPEN
Description
Setting of the tripping torque in direction
CLOSE
Setting of the tripping torque in direction OPEN
Operation mode in direction OPEN
Operation mode in direction CLOSE
Effective distance or end position zone
Peak torque
Behaviour in emergency operation
Torque delay
Torque delay time
Device menu