Device menu
Information
Information
Commands
Parameterization
Enable processes
System events

4.1.2.3. Characteristics

18
File size of event report
The file size of the event report can be modified to record more or less events as
desired. If the file is full, the oldest events will be overwritten so that the latest and
current events are recorded.
Default value: 548 [kByte]
Setting range: 1 ... 1 024 [kByte]
At least 20,000 events can be stored with the max. setting range of 1,024 kByte.
Some events are stored in a sector which cannot be overwritten. This includes, for
example, modifications of the parameter setting, enabling of functions and certain
special functions.
Save interval
The event report is updated and saved at a defined interval. This cycle (saving
interval) can be shortened or extended.
Default value: 50,000 [ms]
Setting range: 1,000 ... 65,535 [ms]
Buffer size
The events are buffered first. From this buffer, they are written to the event report
after the set report cycle. The number of events in the buffer can be set here.
In case of power failure, the events in the buffer will be lost.
Default value: 50 [events]
Setting range: 10 ... 100 [events]
System event filter
The actuator records system events such as operation commands or modifications
on the parameter settings. A filter is used to define the system events to be recorded
in the event report.
Events which can be recorded:
All operation commands recognised as valid and executed are recorded. The
command source of the operation command is also recorded.
All modifications of parameter settings are also recorded. Both the former and the
new value are recorded.
The enabling of a function is recorded.
All important system events are recorded. These include: System start, change of
date, downloads, modifications of the event filter, resetting of operating data and
switching on the mains voltage.
Event filter for Events
The actuator records status signals such as faults, warnings or end position
OPEN/CLOSED. A filter is used to define the status indications to be recorded in the
event report. It is possible to select all fault signals and warnings.
DIS_2249 Diagnostics
DIS_1231 Operational info collection
DIS_313 Characteristics