Duty Type Monitoring; I/O Interface - AUMA PROFOX PF-M25(X) Manual

Hide thumbs Also See for PROFOX PF-M25(X):
Table of Contents

Advertisement

Device menu
4.2.11.

Duty type monitoring

Example:
4.2.12.

I/O interface

52
This function monitors the permissible operation mode of the actuator or the excess
of the
permissible motor running time per hour
permissible motor starts per hour
DIS_53 Configuration
DIS_355 Duty type monitoring
Table 47:
ID
Indication
PRM_2122
Permissible run time
PRM_2123
Permissible starts
If any of these values has been exceeded, the actuator will however not be stopped,
but the a warning is issued. The warnings are automatically deleted as soon as the
permissible running time/h or the permissible starts/h are fallen short of.
In the operational info collection (DIS_1231 Asset Management) the number of
excesses (warnings) as well as the number of motor running times and motor starts
are recorded.
PRM_168 On time warning 1 contains the sum of all on-time warnings.
PRM_167 On time warning 2 contains the maximum duration of an on-time warning
Due to excess of the set running time/h or the set starts/h, the actuator signals 4
times an on-time warning: twice during 5 min, once during 10 min, once during 17
min. Afterwards, the operating data counters contain the following values:
PRM_168 On time warning 1 = 37 min = sum of all times (5+5+10+17 min)
PRM_167 On time warning 2 = 17 min = longest period
Figure 15: Example
[1]
Running time/h
[2]
Starts/h
[3]
On time warning
Permissible run time
Default value: 15 min (minutes)
Setting range: 10 ... 60 min (minutes)
Permissible starts
Default value: 1,200 starts/h
Setting range: 1 ... 1,800 starts/h
DIS_53 Configuration
DIS_139 I/O interface
PROFOX actuators
Description
Monitoring of the permissible running time in
the previous hour
Monitoring of the permissible starts in the pre-
vious hour