12.4
Mode 4: Agent Release, Dual Hazard, Not Cross-zoned, Split
Release
Out1
Signal
Steady
Out2
Signal
Escalating
Out3
Rel.
Releasing
Out4
Rel.
Releasing
RLS TMR 1 Started
RLS Tmr 1 Interrupted
RLS Tmr 1 Cancelled
RLS Tmr 2 Started
RLS Tmr 2 Interrupted
RLS Tmr 2 Cancelled
i
Note:
12.4.1 Zone Configuration
•
Detection Zone -1: Alarm (Hazard Area 1, not cross-zoned)
•
Detection Zone -2: Alarm (Hazard Area 1, not cross-zoned)
•
Detection Zone -3: Alarm (Hazard Area 2, not cross-zoned)
•
Detection Zone -4: Alarm (Hazard Area 2, not cross-zoned)
•
Detection Zone -5: Abort/Manual Release Combination (hazard 1)
•
Detection Zone -6: Abort/Manual Release Combination (hazard 2)
•
NAC -1: Escalating Signal, indicates Hazard Area 1 state
•
NAC -2: Escalating Signal, indicates Hazard Area 2 state
•
RAC -1: Releasing Circuit (Hazard Area 1)
•
RAC -2: Releasing Circuit (Hazard Area 2)
12.4.2 Hazard Configuration
•
Default Release Timer Value:
•
Default Manual Release Delay: 0 seconds.
•
Default Abort Delay Type:
•
Default Soak Timer Value:
12.4.3 NAC Configuration
•
Default Escalating NAC code of Hazard Area State:
•
•
Detection Zones
Z1
Z2
Z3
Alm
Alm
Alm
X
X
X
X
X
X
Dual hazard operation is not permissible for UL/ULC operation.
Hazard Idle: Off
Hazard Alarm: Temporal (see Table 7)
Z4
Z5
Z6
Alm
AB/MR
AB/MR
X
X
X
X
X
X
X
X
X
X
60 seconds
Standard UL.
0 seconds
Pre-Programmed Modes
Phantom Zones
Release Timers
RT1
Zp1
Zp2
Exp
Z1+Z2
Z3+Z4
X
RT2
Exp
X
75