2. Check the ambient temperature. You must be operating within the specifications (see Server
Features and specifications for more information).
3. Make sure that the heat sink for microprocessor n.
4. (Trained technician only) Replace system board.
• 80010b01-0703ffff : Numeric sensor [NumericSensorElementName] going high (upper non-
recoverable) has asserted. (Ambient1 Temp)
This message is for the use case when an implementation has detected an Upper Non-recoverable sensor
going high has asserted.
May also be shown as 80010b010703ffff or 0x80010b010703ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Temperature
SNMP Trap ID
0
CIM Information
Prefix: PLAT ID: 0498
User Response
1. Make sure that the fans are operating, that there are no obstructions to the airflow (front and rear
of the server), that the air baffle is in place and correctly installed, and that the server cover is
installed and completely closed.
2. Check the ambient temperature. You must be operating within the specifications (see Server
Features and specifications for more information).
3. Make sure that the heat sink for microprocessor n.
4. (Trained technician only) Replace system board.
• 80010b01-2701ffff : Numeric sensor [NumericSensorElementName] going high (upper non-
recoverable) has asserted. (Ambient2 Temp)
This message is for the use case when an implementation has detected an Upper Non-recoverable sensor
going high has asserted.
May also be shown as 80010b012701ffff or 0x80010b012701ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Temperature
Lenovo System x3100 M5 Installation and Service Guide